Set up a workspace
A workspace is ready when its instruments send data into series that people can follow and be alerted on. Getting there takes a dozen steps on different screens, and most of them depend on the one before: a location needs a tag, a device needs a location, an alarm needs a series. This page gives the order; each step links to the page that explains it. Example: set up a first site follows the same steps for one site, with real values.
Before you start, the router (gateway) must be installed on site. Your service provider does that; it connects to Cytometa Cloud by itself and waits for approval.
If a service provider commissions the site, the organization administrator first allows service provider access and checks that the name shown is your provider’s. See Allow service provider access.
-
Create the workspace. One per plant, region or project — not one per device. Choose the slug carefully: it cannot be changed later. Organization administrator. Manage workspaces
-
Give the people who set it up access. Assign yourself and the Managers who will do the next steps. Workspace roles are given per user in Settings › Organization Settings › Users. The rest of the team can follow at the end. Organization administrator. Invite and manage users
-
Check the router. Tell Cytometa which workspace the router’s data goes to. The router arrives Approved in that workspace. Get the workspace right the first time: moving a router later unlinks all its devices. Organization administrator. Manage routers
-
Create the tags. Settle the tag scheme —
inlet,outlet,raw— before data arrives; every location and flow needs one, and retagging history is not something you want to do twice. Manager. Manage tags -
Create the locations. One per physical measuring site, with an address that finds its place on the map. A location’s tag cannot be changed later. Manager. Create a location
-
Create the devices. One per instrument, with the MAC address from its label. The router links each device to the instrument it found with that address. Once the router is running, the dashboard also lists the devices it found without a record, so you can add them from there. Manager. Create a device, Add discovered devices
-
Configure each device. Tagging and measurement interval for a Bactosense, transport and channels for a Sicon, the flow schedule for a FlowControl. Manager. Supported devices
-
Check the metrics. Readings with a metric ID the workspace does not know are held, not shown. Add catalog metrics, set units and expected ranges, and resolve anything pending. Manager. Add and edit metrics · Resolve pending metrics
-
Set up gating (flow cytometry sites). Draw a gate on a representative sample and apply it to the series, so counts from the same stream stay comparable. Manager. How gating works · Edit a gate
-
Create the alarms. Start with the few series that matter most, and require two or three consecutive values to avoid alarms on a single noisy reading. Manager. Create an alarm
-
Invite the rest of the team. Give each person the least role that lets them do their job, and have them choose their email notifications. Organization administrator. Roles and permissions · Choose email notifications
-
Save shared views. A view per site or process step gives everyone the same starting point on Metrics. Manager. Save and share a view
Result: the dashboard shows the devices online, the latest metrics and samples arrive, and alarms watch the series that matter.
When the service provider’s work is done and they should not keep access, the organization administrator withdraws it in Allow service provider access.
If data does not arrive
Section titled “If data does not arrive”| Symptom | Where to look |
|---|---|
| The router is not listed | Cytometa has not enrolled it yet - step 3. |
| A device stays without data | Its MAC address does not match what the router discovered — step 6. |
| Data arrives but no series appear | The metric IDs are unknown — step 8. |
More in Troubleshooting.
Related
Section titled “Related”- Example: set up a first site — the same steps for one intake, with values
- Use the setup wizard — steps 4 to 6 in one go
- Roles and permissions